51EN
DIRIS DIGIWARE DC - 545830B - SOCOMEC
13. PERFORMANCE CLASSES
Performance classes are drawn up in compliance with IEC 61557-12
Classication of DIRIS Digiware SD
Temperature K55
Performance class for active power or active energy 1 without adapter / Class 2 with adapter
13.1. Specication of the characteristics
Symbol
Function
Operating performance
class DIRISDigiwareDC in
compliance with IEC 61557-12
Measurement
range
With DIRIS Digiware U-31dc
Pa
Total active power
1 2% … 120% In
Ea
Total active energy
1 2% … 120% In
U
Voltage (DC+/DC-)
0.5 19.2 … 60VDC
I
Current
0.5 10% … 120% In
With DIRIS Digiware U-32dc
Pa
Total active power
1 2% … 120% In
Ea
Total active energy
1 2% … 120% In
U
Voltage (DC+/DC-)
0.5 48 … 180VDC
I
Current
0.5 10% … 120% In
With DIRIS Digiware U-32dc + adapter U500dc
Pa
Total active power
2 2% … 120% In
Ea
Total active energy
2 2% … 120% In
U
Voltage (DC+/DC-)
1 200 … 600VDC
I
Current
0.5 10% … 120% In
With DIRIS Digiware U-32dc + adapter U1000dc
Pa
Total active power
2 2% … 120% In
Ea
Total active energy
2 2% … 120% In
U
Voltage (DC+/DC-)
1 400 … 1200VDC
I
Current
0.5 10% … 120% In
With DIRIS Digiware U-32dc + adapter U1500dc
Pa
Total active power
2 2% … 120% In
Ea
Total active energy
2 2% … 120% In
U
Voltage (DC+/DC-)
1
1200 … 1500 VDC +10%
I
Current
0.5 10% … 120% In