4. 2.1. Installation on raised flooring
If Green Power 2.0 is to be installed on raised ooring, the SOCOMEC adjustable
frame (gure 4.2.1-1) must be used to support the weight of the unit (gure 4.2.1-2).
Refer to the relevant installation manual provided in the packaging for
information on frame assembly operations.
Allow for small openings in the oor panels to ensure the air ow at the front (gure 4.2.1-3).
4. 2.2. Installation over a tunnel
Green Power
2.0
COOL
AIR
COOL
AIR
DOOR
4. 2.3. Heat loss and ventilation characteristics
kVA
airow
Totalairow
Heat losses at full load MAX.
Nominal condition / worst conditions
Bottom Mid height
W BTU/h
UPS 320
45 % * 55 % *
4500 m3/h 17000 / 20000 58006 / 68242
UPS 400 4500 m3/h 22000 / 26000 75066 / 88716
Bypass 250/500
100 % * 0% *
1050 m3/h 2700 9331
Bypass 600/800 900 m3/h 3640 12459
Bypass 900/1200 2000 m3/h 5260 17973
Bypass 1500/2000 2200 m3/h 11600 36120
Bypass 2400
2200 m3/h 16700 50101
*
of Total air
ow