11
ENGLISH
4.2.2-1
4.2.1-2
Green Power 2.0 320 to 400 kVA - Ref.:
INMGP2401210-GB_12
4.2.1-1
4. 2.1. Installation on raised flooring
If Green Power 2.0 is to be installed on raised ooring, the SOCOMEC adjustable
frame (gure 4.2.1-1) must be used to support the weight of the unit (gure 4.2.1-2).
Refer to the relevant installation manual provided in the packaging for
information on frame assembly operations.
Allow for small openings in the oor panels to ensure the air ow at the front (gure 4.2.1-3).
4. 2.2. Installation over a tunnel
4. RequiSiteS
4.2.1-3
Green Power
2.0
COOL
AIR
COOL
AIR
DOOR
4. 2.3. Heat loss and ventilation characteristics
kVA
airow
Totalairow
Heat losses at full load MAX.
Nominal condition / worst conditions
Bottom Mid height
W BTU/h
UPS 320
45 % * 55 % *
4500 m3/h 17000 / 20000 58006 / 68242
UPS 400 4500 m3/h 22000 / 26000 75066 / 88716
Bypass 250/500
100 % * 0% *
1050 m3/h 2700 9331
Bypass 600/800 900 m3/h 3640 12459
Bypass 900/1200 2000 m3/h 5260 17973
Bypass 1500/2000 2200 m3/h 11600 36120
Bypass 2400
2200 m3/h 16700 50101
*
of Total air
ow