Green Power 2.0 320 to 400 kVA - Ref.:
INMGP2401210-GB_12
4. RequiSiteS
4. 9.
protectIon anD cross-sectIon of battery cables
Values are provided for a distance of 5 meters between Green Power 2.0 and the battery. (Battery mean current
while discharging – Please see § 4.6.2). Use double insulated cables BN4-F.
CAUTION: The size of protections depends on the power and back up time of the system. Protections other
than the ones dened below may cause electrical hazard or damage to the equipment.
Exemple of Ur fuse battery protection
1
, block type 90 Ah: SWL2500, XP12V3000
Max Power
UPS output
Backup
time
branches
Number
blocks
Number
4
Ur Fuse
Number
Size of
Ur fuse
Icc mini
batterie
5
Ferraz
Code
Socomec
Code
min. Cross-
section
2
320 kVA
320 kW
5 mn 2 41 2x2 400A T2 4000 A B320483C E045578 2x120 mm²
320 kVA
288 kW
11 mn 3 36 2x2 500A T2 5200 A F320487C E045588 2x150 mm²
320 kVA
256 kW
29 mn 5 36 2x2 550A T2 6300 A
G320488C
E045628 2x240 mm²
400 kVA
400 kW
8 mn 3 43 2x2 500A T2 5200 A
F320487C
E045588 2x150 mm²
15 mn 4 43 2x2 500A T2 5200 A F320487C E045588 2x185 mm²
26 mn 6 43 2x2 630A T2 7400 A H320489C E045568 2x240 mm²
400 kVA
360 kW
3 mn 2 41 2x2 400A T2 4000 A B320483C E045578 2x150 mm²
10 mn 3 42 2x2 500A T2 5200 A F320487C E045588 2x150 mm²
400 kVA
320 kW
15 mn 4 36 2x2 500A T2 5200 A
F320487C
E045588 2x150 mm²
1
not standard Fuse protection FUSOMAT Socomec, please contact us
2
H07 RN-F cabling for a 5 meters distance between the UPS and the battery
4
see 5. 11.1
Circuit breaker Battery protection ( 39 blocs)
Denition for 36 to 39 blocs
Green Power
2.0 Power
Backup
time
Number of
Contact in serie
Size of breaker
Magnetic adjustment
Im = nxIn
ICC battery min.
5
400 kW 30 mn 2 NW10HDC 2100A D+1 notch 2500A
5
end of life