28
Green Power 2.0 320 to 400 kVA - Ref.:
INMGP2401210-GB_12
5. 10.7. Replacement of batteries
When replacing the batteries, please use the same type and number of battery blocks.
Do not dispose of into a fire due to risk of explosion. Do not try to open or break up batteries. The
electrolyte is toxic and may cause acid projections or injuries.
For this operation, we recommend that you contact a SOCOMEC servicing technician.
5. 11.
5. 11.1. Technical specifications
Dimensions (WxDxH): 800 x 830 x 1925 1000 x 830 x 1925
Weight (with packaging): < 1550 kg
Protection level: IP 20
Operating temperature: 0÷40 °C (15÷25 °C recommended for longer battery life)
Storage and transport temperature
1
: -5 °C ÷ +40 °C max (recommended 25 °C)
Relative humidity (condensation-free): up to 95%
Battery recharging:
Tambient≤25°C: every 6 months
25°C≤Tambient≤30°C: every 4 months
30°C≤Tambient≤35°C: every 3 months
35°C≤Tambient≤40°C: every 2 months
Tambient > 40 °C: not recommended
UPS output Power kW: Battery block number:
360 < P ≤ 400 43
320 < P ≤ 360 from 39 to 43
P ≤ 320 from 36 to 43
1
General indication for the application of lead batteries. For further details, see the battery manufacturer’s indications.
5. 11.2. Reliability
Conforms to Standards: IEC 50272-2, IEC 62040-1-1
5. 11.3. Storage
The duration of storage batteries must not exceed 6 months in appropriate storage conditions. The batteries
should be stored away from bad weather in space whose average temperature is between 30 °C and -5 °C,
with a maximum temperature below 40 °C. A battery is Rechargeable considered without signicant decrease
in reliability, while his last rell does not date from more than 6 months.