6
Green Power 2.0 320 to 400 kVA - Ref.:
INMGP2401210-GB_12
• Do not connect the output neutral to ground (except the TNC Option). DELPHYS does not modify the neu-
tral arrangements of the system; the use of an isolation transformer is required should it be necessary to
modify the neutral arrangements downstream of DELPHYS (see § 4.5.1 " Connecting earth cables").
• If DELPHYS needs to be scrapped, it is essential to entrust the equipment solely and exclusively to spe-
cialist disposal companies. These are obliged to break up and dispose of the various components in ac-
cordance with the legal provisions in force nationally.
• Before connecting the external battery cabinet, check that this is fully compatible with the model of
DELPHYS.
• The use of external battery cabinets not supplied by the manufacturers is not recommended.
• Switch off and isolate DELPHYS and then wait for 5 minutes before removing the protection panels in or-
der to carry out work on parts under dangerous voltage.
• Danger of explosion if the batteries are replaced with others of the wrong type.
• The batteries are considered as toxic waste. If they are replaced, entrust the used batteries solely and
exclusively to specialist disposal companies. As provided for by the local laws in force, batteries must not
be disposed of with other industrial or domestic waste.
It is very dangerous to touch any part of the batteries as there is no isolation between the batteries
and the mains power source.
The product you have chosen is designed for commercial and industrial use only. In order to be used for particu-
lar “critical applications” such as life support systems, medical applications, commercial transportation, nuclear
facilities or any other application or systems where product failure is likely to cause substantial harms to person
or property, the products may have to be adapted. For such uses we would advise you to contact SOCOMEC
beforehand to conrm the ability of these products to meet the requested level of safety, performance, reliability
and compliance with applicable laws, regulations and specications.
This is a product for commercial and industrial application in the second environment – installation
restrictions or additional measures may be needed to prevent disturbances.
2. 2.
DescrIptIon of the symbols useD on the labels applIeD to the unIt
All the precautions and the warnings on the labels and plates on the inside and outside of the equipment should
be respected.
DANGER! HIGH VOLTAGE (BLACK/YELLOW)
GROUND TERMINAL
READ THE USER MANUAL BEFORE USING THE UNIT
2. Safety