8. 3. UPs idEntification: addrEss 0x1100, 32 words
Code Description Number Address Type Remarks
I000 UPS identication 10 WORDS 0x1100 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I010 UPS Description 6 WORDS 0x110A 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I016 Location 6 WORDS 0x1110 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
I022 Serial number 10 WORDS 0x1116 1 word = 2 ASCII codes MSB = 1. Char, LSB = 2. Char
8. 4. datE & HoUrs: addrEss 0x1360, 4 words
Code Description Number Address Type Remarks
D00 Minutes / seconds 1 WORDS 0x1360 Byte value MSB = minutes, LSB = seconds
D01 Hours / day 1 WORDS 0x1361 Byte value MSB = day, LSB = hours
D02
Month / day of
week
1 WORDS 0x1362 Byte value
MSB = month,
LSB = day of the week
1=Monday...7=Sunday
D03 Year 1 WORDS 0x1363 00 = 2000
8. 5. UPs configUration: addrEss 0x1120, 16 words
Code Measurements Unit Address Remarks
T000 Kind of equipment 0x1120
1= single unit, 3= parallel + centralised bypass
6 = modular parallel system
T001 UPS output power kVA 0x1121
T002 Unit output power kVA 0x1122
T003 Unit number 0x1123 1 - 8
T004 Number of Unit 0x1124 1 - 8
T005 UPS redundant 0x1125 0 - 1
T006 With battery 0x1126 0 - 1
T007 With ywheel 0x1127 0 - 1
T008 0x1128
T009 With genset 0x1129 0 - 1
T010 0x112A
T011 0x112B
T012 0x112C
T013 With rectier input supply 0x112D 0 - 1
T014 Single 0x112E 0 = Tri, 1 = Single
T015 Measurements management 0x112F 0 = x 1, 1 = x 10
sIngle UnIt UPs modbUs tables
13
Delphys green power - Ref.:
IOMDGPJB0910-GB_11
ENGLISH