8. 7. Unit aLarms: addrEss 0x114a, 4 words
Code Description Bit Address Remarks
A032 Unit Imminent stop 0 0x114A
A033 Unit overload 1
A034 Transfer blocked 2
A035 Transfer impossible 3
A036 Insufcient Resources 4 Only on parallel
A037 5
A038 6
A039 Rectier critical 7
A040 Inverter critical 8
A041 Bypass critical 9
A042 Common critical 10
A043 FAN alarm 11
A044 Back feed protection open 12
A045 ACS synchro source fault 13
A046 14
A047 15
A048
Operating on battery
0 0x114B
A049 Battery alarm 1
A050 Battery room 2
A051 Battery discharged 3
A052 End of autonomy time 4
A053 Battery test failure 5
A054 Earth leakage fault 6
A055 Battery circuit open 7
A056 On battery with mains OK 8
A057 DC voltage not OK 9
A058 Rectier preventive 10
A059 Inverter preventive 11
A060 Bypass preventive 12
A061 Common preventive 13
A062 Mimic panel 14
A063
Ambient T° max
15
A064 0 0x114C
A065 1
A066 2
A067 3
A068 4
A069 5
A070 6
sIngle UnIt UPs modbUs tables
16
Delphys green power - Ref.:
IOMDGPJB0910-GB_11