10. 8. UPs aLarms: addrEss 0x0148, 2 words
Code Description Bit Address Remarks
A000 UPS imminent stop 0 0x0148
A001 UPS overload 1
A002 UPS transfer blocked 2
A003 UPS transfer impossible 3
A004 UPS insufcient Resource 4
A005 UPS Redundancy loss 5
A006 Parallel fault 6
A007 7
A008 8
A009 UPS: Battery alarm 9
synthesis of all unit
alarms
A010 UPS on battery 10
A011 UPS: Battery discharge 11
A012 UPS: End of autonomy 12
A013 UPS: Temperature alarm 13
A014 14
A015 15
A016
Module 1 general
0 0x0149
A017 Module 2 general 1
A018 Module 3 general 2
A019 Module 4 general 3
A020 Module 5 general 4
A021 Module 6 general 5
A022 Module 7 general 6
A023 Module 8 general 7
A024 8
A025 9
A026 10
A027 11
A028 12
A029 13
A030 Bypass alarm 14
A031 15
modbUs In Parallel system wIth centralIsed byPass
30
Delphys green power - Ref.:
IOMDGPJB0910-GB_11