9. SPECIFICATIONS
9.1. UPS block diagram
Bypass
Input
filter
Charger Battery
AC/DC
Boost
DC/AC
Inverter
DC/DC
Output
filter
9.2. UPS specications
Output short-circuit current (RMS) and protect time (the time within the UPS is able
to sustain the short circuit current):
MODEL
BYPASS MODE NORMAL MODE/BATTERY MODE
SHORT-CIRCUIT
CURRENT (RMS)
PROTECT TIME
SHORT-CIRCUIT
CURRENT (RMS)
PROTECT TIME
1K/1KS 550A 2.8ms 20A 100ms
2K/2KS 698.6A 7ms 35.6A 100ms
3K/3KS 698.6A 7ms 54A 100ms