ITYS 1-3 kVA - 551430A - SOCOMEC
12
EN
Product safety
UPS enclosure IP rating IP20.
CAUTION - To reduce the risk of re, the unit connects only to a circuit
provided with branch circuit overcurrent protection for: 20A rating,
for Tower 3KS models, Type C.
The upstream circuit breaker for Normal AC/Bypass AC must be easily accessible.
For PERMANENTLY CONNECTED EQUIPMENT, a readily accessible
disconnect device should be placed externally to the equipment
For PLUGGABLE EQUIPMENT, the socket-outlet should be installed near the
equipment and should be easily accessible
Check that the indications on the rating plate correspond to your AC powered
system and to the actual electrical consumption of all the equipment to be
connected to the system.
Never install the system near liquids or in an excessively damp environment.
Never allow a foreign body to penetrate the system.
Never block the ventilation grates of the system.
Never expose the system to direct sunlight or source of heat.
If the system must be stored prior to installation, storage must be in a dry place.
The admissible storage temperature range is -25°C to +55°C without batteries,
0°C to +40°C with batteries.
This UPS can be used in TN/IT/TT power systems.