ITYS 1-3 kVA - 551430A - SOCOMEC
25
EN
3.6. User settings
The following table displays the options that can be changed by the user.
SUBMENU AVAILABLE SETTINGS DEFAULT SETTINGS
Language
English, Italiano, Français, Deutsch, Español,
Português, Svenska, Русский, Polski, 简体中文
English
Audible alarm [enabled], [disabled] enabled
Output voltage [200V], [208V], [220V], [230V], [240V]
[230V]
[240V] for AU
Output frequency
In normal mode: [autosensing]
In converter mode: [50Hz], [60Hz]
autosensing
High efficiency mode [disabled], [enabled] disabled
Start/Restart
Cold start: [disabled], [enabled]
Auto restart: [disabled], [enabled]
Start on bypass: [disabled], [enabled]
enabled
enabled
disabled
Site wiring fault [enabled], [disabled] disabled
Overload pre-alarm [50%~105%] 105%
External battery
[Auto detection],
[Manual Ah: 7~144Ah]
Auto detection
0 Ah
Charger current [2A], [4A], [6A], [8A] for long backup model 4A
Dry in Signal [Disabled], [Remote on], [Remote off], [Forced bypass] disabled
Dry out Signal
[load powered], [on bat], [Low bat], [bat open],
[bypass], [ups ok]
bypass
Ambient temperature alarm [enabled], [disabled] enabled
Battery remaining time [enabled], [disabled] enabled
Backup time limit [enabled: 30min.~999min.], [disabled]
Standard: disabled
ES: enabled 60 min.
Date / Time dd/mm/yyyy hh:mm 01/01/2020 00:00
LCD contrast 0 - 100% 50%
Note: if the UPS is used in IT neutral systems, the site wiring fault
function should be disabled.