ITYS 6-10 kVA - 551431A - SOCOMEC
23
EN
The following table shows the Buttons status and description:
BUTTONS FUNCTION DESCRIPTION
Power on
The Unit can be turned on by pressing the button for more than
100 milliseconds and less than 1 second, without utility input and
battery connected
Turn on Press the button more than 1 second to turn on the UPS
Turn off Press the button more than 3 seoconds to turn off the UPS
Scroll up Press to scroll up the menu option
Scroll down Press to scroll down the menu option
Enter menu Select/Confirm the current selection
ESC
Exit the present menu
Press to exit present menu to main menu or the higher-level
menu without changing the setting
Mute buzzer
Press the button to mute the buzzer temporarily; once a new
warning or fault is active, the buzzer will be activated again
NO. STATUS ALARM
1 Battery mode Beep once every 4 sec
2 Battery mode with battery low Beep once every sec
3 Bypass mode Beep once every 2min
4 Overload Beep twice every sec
5 Warning active Beep once every sec
6 Fault active Beep continuously
7 Button function active Beep once
The buzzer will be temporality silenced if one or more alarms are active and silence
button is pressed. The buzzer will beep again if any new alarm becomes active.
Backlight
The LCD backlight automatically dims after 10 minutes of inactivity.
Press any button to restore the screen.