EasyManua.ls Logo

socomec ITYS ITY3-TW060B - User Settings

socomec ITYS ITY3-TW060B
46 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ITYS 6-10 kVA - 551431A - SOCOMEC
26
EN
3.7. User settings
The following table displays the options that can be changed by the user.
SUBMENU AVAILABLE SETTINGS DEFAULT SETTINGS
Language
English, Italiano, Français, Deutsch, Español,
Português, Svenska, Русский, Polski, 简体中文
English
Audible alarm [enabled], [disabled] enabled
Output voltage [220V], [230V], [240V]
[230V]
[240V] for AU
Output frequency
In normal mode: [autosensing]
In converter mode: [50Hz], [60Hz]
autosensing
High efficiency mode [disabled], [enabled] disabled
Auto bypass [disabled], [enabled] enabled
Start/Restart
Cold start: [disabled], [enabled]
Auto restart: [disabled], [enabled]
enabled
enabled
Site wiring fault [enabled], [disabled] disabled
Overload pre-alarm [50%~105%] 105%
External battery
[Auto detection],
[0~300Ah]
Auto detection
0Ah
Charger current
1-4A for 6-10K
2-12A for 6-10KS
1.4A for 6K
2A for 8.5-10K
4A for 6-10KS
Dry in signal
[Disabled], [Remote on], [Remote off],
[Forced bypass]
disabled
Dry out signal
[load powered], [on bat], [Low bat], [bat open],
[bypass], [ups ok]
bypass
Ambient temperature alarm [enabled], [disabled] enabled
Battery remaining time [enabled], [disabled] enabled
Date / Time dd/mm/yyyy hh:mm 01/01/2020 00:00
LCD contrast 0 - 100% 50%
Note: if the UPS is used in IT neutral systems, the site wiring fault
function should be disabled.

Related product manuals