ITYS 6-10 kVA - 551431A - SOCOMEC
36
EN
5.5.3. Access to battery connector (DC source to UPS)
1. Make sure the UPS is completely off before connecting or disconnec-
ting the EBM.
2. Before connecting the EBM, make sure that the number of battery
sections and capacity are the same as the LCD setting.
3. Do not reverse the polarity of the external battery.
Connect EBM to UPS with ‘Battery cable’ and ‘EBM detection cable’:
Note:
1. Extended runtime with up to 6 Extended Battery Modules (EBMs)
per UPS.
2. If more than 2 EBMs are connected to the UPS, an additional cable
of ground (10mm
2
) must be connected between UPS and EBMs.