46
MASTERYS BC 15-40 kVA - Ref.: IOMMASBCXX09-EN 01
11. TECHNICAL SPECIFICATIONS
1. 360 V with Pout = 90% Pn.
2. Initial Condition Pout ≤ 80% Pn
3. @ Battery Fully Discharged. Call SOCOMEC support service.
4. @ Battery Fully Charged. Call SOCOMEC support service.
Models 15 20 30 40
Input/Output phases 3/1 and 3/3 3/1 and 3/3 3/3 3/3
Electrical specifications - Input
Mains voltage Vin 3Ph+N 400 V -15% +20% (up to -40% @50% of nominal load)
Input frequency Hz 50-60 ±10%
Input power factor > 0.99 (three phase)
THDI < 3%
Electrical specifications - External battery
Battery voltage range V bat from +/-175
3
up to +/-360
4
Vdc
Electrical specifications - Output
Output voltage
(three phase + neutral)
V
230 single phase (selectable: 208/220/230/240 V) ±1%
1
400 three phase (selectable 360/380/400/415 V) ±1%
1
Frequency Hz 50-60 ±2% (from 1% to 8% if generator is used)
Automatic bypass
nominal output voltage ±15%
(from 10% to 20% selectable if generator is used)
Nominal power kW 13,5 18 27 36
Overload
(@ 25 °C; Vin >
380; Vbat > 216)
2
• 10 minutes
• 1 minute
kW
16,875
20,25
22,5
27
33,75
40,5
45
54
Crest factor ≥ 2.7
Voltage distortion 1% with linear load
Environment
Operating temperature °C 0÷35 (15÷25 recommended for longer battery life)
Storage temperature °C -5÷45
Relative humidity % 0÷95 condensation-free
Max. altitude m 1.000 without derating; 3.000 max
Acoustic noise dBA < 52 < 52 < 55 < 55
Required cooling capacity m
3
/h 280 280 465 465
Dissipated power max W 883 1211 1706 2142
Dissipated power max BTU/h 3016 4135 5823 7250
Standards
Safety EN 62040-1/A1, EN 60950-1
Type and performance EN 62040-3 (VFI-SS-111)
EMC EN 62040-2 (Category C2)
Product certifi cation CE - TÜV-SÜD
Protection level IP20, IP21 on request
Mechanical characteristics with standard batteries
Models
T
Dimensions mm 444 x 795 x 1400
Weight kg 390÷540
M
Dimensions mm 444 x 795 x 1000
Weight kg 230÷315
S
Dimensions mm 444 x 795 x 800
Weight kg 190÷200