Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
6. CONTROL PANEL
Luminous
status bar
Power module LED
indicators
Bypass module LED
indicator
LED indicator
Colour Power module Bypass module
Green Module on inverter Bypass ready to start
Flashing green - Load on bypass
Yellow Module ready to start Maintenance bypass
Flashing yellow Module initialising
Load on inverter or bypass and transfer impossible/
locked
Red Module stopped due to alert Bypass alert present
Flashing red Initialising failure Bypass blocked with alert
Flashing green yellow and
red
No communication No communication
Control panel luminous status bar indicator
Colour Status
Flashing red-yellow-green-red
No communication. The data is no longer updated or not
present.
Load status cannot be given.
Flashing red Load supplied, but the output will stop in few minutes.
Red Load not supplied: Output switched OFF due to an alarm.
Flashing yellow-red Load supplied, but no longer protected. A critical alarm occurs.
Flashing yellow Maintenance request / in progress.
Yellow Load supplied with warning.
Flashing green-yellow-green Load supplied and preventive alarm present.
Flashing green Load going to be supplied and testing.
Green Load protected in inverter.
Grey (OFF) Load not supplied output on standby / isolated / OFF.