34 EN
Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
Item Description
Rules of animation
Touch actions
Grey Green Yellow Red
1
Rectifier input supply Not present Present
Out of toler-
ance
--
2
Rectifier status
Normal
status
-
Preventive
alarm
Critical alarm
Access to input
measurements page
3
DC voltage bus
DC voltage
absent
DC voltage
presence
-- -
4
Inverter status
Normal
status
-
Preventive
alarm
Critical alarm
Access to inverter
measurements page
5
Inverter output Inverter OFF Inverter ON
Inverter on
battery
--
6
Maintenance bypass * MBP present -
Load on
maintenance
bypass
--
7
Bypass input * Not present Present
Out of toler-
ance
--
8
Bypass status *
Normal
status
-
Preventive
alarm
Critical alarm
Access to bypass
page
9
Load rate symbol
No load
Fill-up to
95%
Fill-up to
110%
Fill-up over
110%
Access to output
measurements pages
10
Load rate value Instantaneous value. displayed if value > 0 -
11
DC battery input **
DC voltage
absent
DC voltage
presence
BCR function
running
--
12
DC battery output **
DC voltage
absent
DC voltage
presence
Inverter on
battery
-
13
Battery indicator **
-
Fill-up to
100%
Fill-up to
45%
Fill-up to
15%
Access to bat. meas-
urements page
14
Battery charging /
discharging **
-
Battery
charging
Battery
discharging
-
-
15
Battery level or remain-
ing backup time during
battery discharge **
Instantaneous value. displayed if value > 0
The backup time is no more displayed if it is below two
minutes.
-
16
Shared battery symbol not present if each unit has its own battery. ** -
* Element disappears if converter mode is active
** Not present if batteries are not present