Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
8. OPERATING PROCEDURES
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care-
fully.
NOTE: with the stop procedure the load will be disconnected.
8.1 SWITCHING ON
Connect the mains to the UPS.
• Put switch Q1 (or the external input mains switching device) into position 1.
Wait for the display to switch on.
• Enter MAIN MENU > COMMANDS > UPS PROCEDURES.
• Select Automatic Start Procedure and press ENTER.
Carry out the operations indicated on the display.
8.2 SWITCHING OFF
This operation interrupts the power supply to the load. The UPS and the battery charger will be shutdown.
• Enter menu MAIN MENU > CONTROLS > UPS PROCEDURE.
• Select Automatic Stop Procedure and press ENTER.
Wait approx. 2 minutes for the UPS shutdown.
NOTE: the controlled shutdown of each server connected to the LAN can be managed by shut-
down software (only with Net Vision option card).
Carry out the operations indicated on the display. This operation cannot be aborted.
8.3 BYPASS OPERATIONS
Available only with external manual bypass.
SWITCHING ONTO MAINTENANCE BYPASS
This operation creates a direct connection between the UPS input and output, excluding the equipment control part.
This operation is performed in the event of:
- standard maintenance.
- serious failure has occurred.
WARNING! This operation interrupts temporarily the power supply to the load.
WARNING! LOAD POWERED BY INPUT MAINS!
Your load is exposed to mains disturbances.
• Enter menu MAIN MENU > CONTROLS > UPS PROCEDURE.
• Select Automatic Stop Procedure and press ENTER.
Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
- carry out the procedure described above;
- put the switch to position 1.