Operating modes 'MODULYS GP' 100 kW UL - Ref.: IOMMODGPXX09-EN 03
2. ENVIRONMENTAL REQUIREMENTS AND HANDLING
NOTE!
Before carrying out any operations on the unit read the 'Safety standards' chapter carefully.
2.1 ENVIRONMENTAL REQUIREMENTS
The room must be:
of a suitable size
free from conductive, inflammable and corrosive items;
not exposed directly to sunlight.
The floor must support the weight of the unit and guarantee its stability. The unit is designed for indoor installation
only.
Check that the UPS will not be installed in a dusty environment.
ROOM POSITIONING
Top view: rear air outlet Top view: top air outlet
(1)
130°
≥ 5 ft
≥ 1.25 ft
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS
door
free area
free area
130°
≥ 5 ft
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS
door
free area
Front view: rear or top air outlet
≥ 0.5 ft
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS OR
OTHER
CABINET
UPS
UPS OR
OTHER
CABINET
free area
1. This configuration is possible only with top air-exhaust option. See 'Standard features and options' chapter.