17
NETYS PR RACK 1U - Ref.: IOMNETPRXX01-GB 02
ENGLISH
11. TECHNICAL SPECIFICATIONS
Models PR 1000 Rack 1U PR 1500 Rack 1U
Power (VA) 1000 1500
Power (W) 670 1000
Electrical specifications - Input
Voltage 230 V (default); 220 V, 230 V, 240 V selectable
Frequency 45÷65 Hz, 50/60 Hz auto-sensing
Mains connection IEC 320 (10 A)
Electrical specifications - Output
Voltage (in Normal Mode with AVR) • •
Voltage (in Battery Mode) Same as selected nominal input voltage: 220 V, 230 V, 240 V ±5% (-10% after Battery Low)
Frequency 50/60 Hz
Wave form Sine wave
Transfer time 2-4 ms (typical)
Normal Mode protections overload (110% for 3 minutes); shortcircuit protected
Battery Mode protections overload (110% for 30 seconds); shortcircuit protected
Load connection socket IEC 320 (4) 10 A
Battery
Typical back-up time 12 minutes
Battery recharge
Advanced charging for faster recovery. Approximately 3 hours to 90% usable capacity at
nominal line and no supplementary power supply load).
Reporting and Communication
Communication interface
RS232 - USB
Ethernet adapter
NET-VISION (TCP/IP & SNMP) optional card
Local communication software UniVision (management software)
Remote communication software UniVision Pro (management software)
Data line protection
NTP data line suppressor: RJ45 10 Base T
Environment
Noise level (normal mode) < 45 dBA (at 1 meter)
Temperature 0÷40 °C (10÷25 °C for optimum battery life)
Environment Altitude: 2000 m, humidity: 95% non-condensing
Reference standards (EN) IEC62040-1-1 (safety), EN 62040-2 (EMC), EN 61000-4-5/C62.41:1991 (surge)
Mechanical characteristics
Dimensions (WxDxH mm) 440 x 578 x 44,5
Net weight (kg) 21 23