SOFAR 1.1K~3.3KTL-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
- 27 -
Figure 4-9 NOT allowed: connect loads between inverter and circuit breaker
Table 4-2 Recommended AC output cable specifications
Model
SOFAR
1100TL-G3
SOFAR
1600TL-G3
SOFAR
2200TL-G3
SOFAR
2700TL-G3
SOFAR
3000TL-G3
SOFAR
3300TL-G3
Cable(Copper)
4mm²
4mm²
4mm²
6mm²
6mm²
6mm²
Breaker
16A/400V
16A/400V
25A/400V
25A/400V
25A/400V
25A/400V
Multi core copper wire
AC cable should be correctly sized to
ensure the power loss in AC cable is less than
1% of the rated power. If the resistance of the
AC cable is too high, it will cause a huge
increase in the AC voltage, which may lead to a
disconnection of the inverter from the electrical
grid. The relationship between power loss in AC cable and wire length, wire cross
sectional area is shown in the following figure
Figure 4-10 wire length, wire cross sectional area and wire power loss