SOFAR 15~24KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
- 54 -
Australia C
Voltage
207
215
253
260
Inverter output (P) % of S
rated
20%
100%
100%
20%
Default volt-var settings for different regions are shown in the following table:
Region
Default value
V
V1
V
V2
V
V3
V
V4
Australia A
Voltage
207
220
240
258
Inverter reactive output
(Q) % of S
rated
44% supplying
0%
0%
60% sinking
Australia B
Voltage
205
220
235
255
Inverter reactive output
(Q) % of S
rated
30% supplying
0%
0%
40% sinking
Australia C
Voltage
215
230
240
255
Inverter reactive output
(Q) % of S
rated
44% supplying
0%
0%
60% sinking
5. On-Off Control
Inverter on-off local control.
6. Set Energy
Set the total power generation. You can modify the total power generation
through this option.
7. Set address
Set the address (when you need to monitor multiple inverters
simultaneously)Default 01.
8. Set Input mode
SOFAR 15~24KTLX-G3 has 2 MPPT circuit, each MPPT circuit can work
interdependently, or divided into parallel mode. User can change the setting
according to the configuration.
9. Set Language
Set the inverter display language.
10. Set AntiReflux
Enable or disable Reflux. It is use for inverter generation and output limit
control functions, but requires the use of external measuring equipment to obtain