SOFAR 15~24KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
Remote control enables. If it is not
controlled by yourself, please
disconnect the DC switch of the
inverter, wait for 5 minutes, and
then turn on the DC switch.
Observe whether the fault has been
eliminated after the inverter is
restarted. If not, please contact the
customer service of SOFARSOLAR.
Inverter shows ID83 when remote
derating. If no one operate this
function, please check the
connection (I/O) according to
chapter 4.5
Logical interface
derating
Check whether the inverter has
dust and dust, whether there are
foreign matters blocking the fan at
the air inlet. If so, please improve
the ventilation and heat dissipation
of the environment. It is
recommended that the inverter
should be cleaned once every half a
year.
String fuse open
circuit alarm
There are internal faults of inverter,
turn OFF the “DC switch”, wait for 5
minutes, then turn ON the “DC
switch”. Check whether the fault is
rectified. If no, please contact
technical support.