SOFAR 3K~6KTLM-G3 User manual
Copyright © Shenzhen SOFAR SOLAR Co., Ltd
live part in the worst-case rated operating condition when used as intended.
DC switch parameters
Rated impulse withstand voltage
Rated operational current (Ie)
1100V/5A, 1000V/8A,
800V/12.5A, 500V/25A
Rated short time withstand current (Icw)
Rated short-circuit making capacity (Icm)
PV terminal parameters
Rated operational current
Maximum temperature limit
4.2. Connecting PGND Cables
Connect the inverter to the grounding electrode using protection ground (PGND)
cables for grounding purpose.
The inverter is transformer-less, requires the positive pole and negative
pole of the PV array are NOT grounded. Otherwise it will cause inverter
failure. In the PV power system, all non current carrying metal parts
(such as: PV module frame, PV rack, combiner box enclosure, inverter
enclosure) should be connected to earth.
Prerequisites:
The PGND cables are prepared ( ≥4mm²outdoor power cables are recommended
for grounding purposes), the color of cable should be yellow-green.