Figure 4-4 Inverter external grounding instruction diagram
4.3. Connect grid side of inverter (AC-Output)
SOFAR 15~24KTLX-G3 connect to utility grid by using AC power cable. The AC
connection must meet the requirement of local grid operator
Ban multiple Inverters use one circuit breaker
Ban connect loads between inverter and circuit breaker
Must use five core outdoor cable, the recommend AC cable and Residual current
breaker (RCB) as below table:
Cross section
area of Cu cable
(mm
2
)
Muti-core
outdoor cable
(mm)
AC Circuit Breaker
specification
40A/230V/3P current
leakage protection 0.1A
40A/230V/3P current
leakage protection 0.1A
50A/230V/3P current
leakage protection 0.1A
1. M6 screw 2. OT terminal 3. threaded hole