ME3000SP User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd
11. Auto Test (For Italian Market Only)
6.Function to Set Country
15. Safety Param. Settings
10*. Empty Discharged (V)
Note: 2*/8*/10*/11* settings are only for DEFAULT battery type.
Select “1. Battery Parameter” and press “OK”, “input password” is shown. Input the password (normal
“0001”, advanced ”0715”), press “Up” or “Down” to change the 1st digit, press “OK” to switch to next digit, when
“0001 / 0715” is shown on the screen, press “OK” to enter “Battery Parameter” interface. If “Incorrect, Try
Again!” is shown on the screen, press “Back” and input the password again.
1) Battery Type (refer to Set battery type)
Select the corresponding battery type.
2) * Battery Capacity (only for DEFAULT battery type)
Input the value of battery capacity.
Input the value of Discharge Depth & EPS Discharge Depth per battery specification.
Discharge Depth
50%
EPS Discharge Depth
80%
For example: if Discharge Depth = 50% & EPS Discharge Depth = 80%. While electric grid is connected:
ME3000SP won’t discharge the battery when its SOC is less than 50%.
In case of blackout: ME3000SP will work in EPS mode (if EPS mode is enabled) & keep discharging the
battery till battery SOC is less than 20%.
Input the value of Max. Charge (A) per battery specification.
Input the value of Over (V) Protection per battery specification.
Input the value of Max. Charge (V) per battery specification.
Input the value of Max. Discharge (A) per battery specification.
8) * Low (V) Protection (only for DEFAULT battery type)
Input the value of Low (V) Protection per battery specification.
Input the value of Min. Discharge (V) per battery specification.
10) * Empty Discharged (V) (only for DEFAULT battery type)