temperature.
ID65
Unrecover
HwAcOCP
The grid current is
too high, and has
cause unrecoverable
hardware fault
ID65-ID70 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check whether
the fault is rectified. If no, please contact
technical support.
ID66
Unrecover
BusOVP
The bus voltage is
too high, and has
cause unrecoverable
fault
ID67
Unrecover
IacRms
Unbalance
The grid current is
unbalance, and has
cause unrecoverable
fault
ID68
UnrecoverIpv
Unbalance
The input current is
unbalance, and has
cause unrecoverable
fault
ID69
UnrecoverVbus
Unbalance
The bus voltage is
unbalance, and has
cause unrecoverable
fault
ID70
Unrecover
OCPInstant
The grid current is
too high, and has
cause unrecoverable
fault
ID71
UnrecoverPv
ConfigSetWrong
Incorrect input
mode
Check the input mode(parallel mode/
independent mode) setting of inverter according
to Section 6.3 (C) 6.Input Mode of this user
manual, If it’s incorrect, change it according to
Section 6.3 (A) 10.Set Input mode of this manual
ID74
UnrecoverIPV
Instant
The input current is
too high, and has
cause unrecoverable
fault
ID74-ID77 are internal faults of inverter,
turn OFF the “DC switch”, wait for 5 minutes,
then turn ON the “DC switch”. Check whether
the fault is rectified. If no, please contact
technical support.
ID75
UnrecoverWRIT
EEEPROM
The EEPROM is
unrecoverable
ID76
UnrecoverREAD
EEPROM
The EEPROM is
unrecoverable
ID77
UnrecoverRelay
Fail
Relay has happen
permanent fault
ID81
OverTemp
Derating
The inverter has
derated because of
the temperature is
too high
Ensure the installation position and
installation method meet the requirements of
Section 3.4 of this user manual. Check whether
the ambient temperature of the installation
position exceeds the upper limit. If yes, improve
ventilation to decrease the temperature.
ID82
OverFreq
Derating
The inverter has
derated because of
the grid frequency is
too high
Inverter automatically reduce the output
power when the frequency of electrical grid is
too high.Please make sure the grid frequency is
within the acceptable range.