IDID NameName DescriptionDescription SolutionSolution
0606
OVRT OVRT function dis-
rupted
If the alarm occurs occasionally,
the possible cause is that the elec-
tric grid is abnormal occasionally.
Inverter will automatically return to
normal operating status when the
electric grid’s back to normal.
If the alarm occurs frequently,
check whether the grid voltage/
frequency is within the acceptable
range. If yes, check the AC circuit
breaker and AC wiring of the
inverter.
If the grid voltage/frequency is
NOT within the acceptable range
and AC wiring is correct, but the
alarm occurs repeatedly, contact
technical support to change the
grid over-voltage, under-voltage,
over-frequency, under-frequency
protection points after obtaining
approval from the local electrical
grid operator.
0707
LVRT LVRT function dis-
rupted
0808
IslandFault Island protection error
0909
GridOVPInstant1 The input voltage is
too high
1010
GridOVPInstant2 Input current is not
symmetrical
1111
VGridLineFault Power grid line
voltage error
1212
InvVoltFault Inverter voltage error
Internal faults of inverter, switch
OFF inverter, wait for 5 minutes,
then switch ON inverter. Check
whether the problem is solved.
If no, contact technical support.
1313
Re󰘱uxFault Anti-countercurrent
overload
Installation and User Manual 57/78
Troubleshooting