AC Frequency 50/60 ± 5 Hz
Maximum Continuous Output Current in Backup
Operation
(4)
14 19 23 28 34 41.5 A
Input - DC (PV and Battery)
Transformer-less, Ungrounded Yes
Max Input Voltage 480 Vdc
Nom DC Input Voltage 380 400 Vdc
Ground-Fault Isolation Detection 600kohm Sensitivity
2-pole Disconnection Yes
Maximum DC PV Power 6000 8000 10000 12000 16500 20000 W
Max Input Current
(5)
8.5 11 14 16.5 22.5 27.5 Adc
Maximum Inverter efficiency 99.2 %
European Weighted Efficiency 98.8 99 %
Reverse-Polarity Protection Yes
Battery Storage
Supported Battery Types SolarEdge Energy Bank, LG RESU10H Prime, LG RESU16H Prime
Number of Batteries per Inverter
Up to 3 SolarEdge Energy Bank Batteries or up to 2 LG Prime
batteries
(6)
Continues Power Up to inverter rated backup power W
Smart Energy Capabilities
Consumption Metering Built-in
(7)
SolarEdge-Single Phase Energy Hub Inverter MAN-01-00812-1.1
63