refer to for LED troubleshooting, or contact SolarEdge support with the Battery
module SN and the LED sequence. Until this is solved, do not proceed with the
installation.
Figure 19: Battery LED indicators
1 Battery Capacity/ Alarm ID
2 Indication LED
3 Operation Indicator
4 Power/Reset Button
CAUTION!
Before turning on the battery module circuit breaker, make sure that the
cables to the inverter are connected, with the DCcables, to the inverter at
the right polarity. Failing to do so, may cause either the battery or the
inverter to malfunction.
10.
Turn on the battery module circuit breaker.
11.
Close the side door and route all the cables above the door.
12.
After turning on the CB, hou will be able to fasten the side door with the three
screws.
Home Battery 48V Installation Guide MAN-01-00954-1.1
26Connecting a Single Battery Module