Appendix B: Technical Specifications
SolarEdge Installation Guide MAN-01-00057-2.2
58
Appendix B: Technical Specifications
Single Phase Inverters
SE2200
SE3000
SE3500
SE4000
SE4000-
16A
SE5000
SE6000
Unit
Output
Rated AC power output
2200
3000
3500
4000
4000
5000
1
6000
W
Maximum AC power
output
2200
3000
3500
4000
4000
5000
1
6000
W
AC output voltage
(nominal)
220/230
Vac
AC output voltage range
184 264.5
Vac
AC frequency(nominal)
50/60 5
Hz
Maximum continuous
output current
12
16.5
2
19.5
2
22
16
27
27
A
Max. continuous
overcurrent protection
12
16.5
2
19.5
2
22
16
27
27
A
Residual current
detector/ Residual
current step detector
300/30
mA
Inrush current AC
(Peak/Duration)
57.5/0.6
A/ms
Max. output fault current
38
A
Power factor range
+/- 0.9 to 1.0
Protective class
Class I
Utility monitoring,
islanding protection,
country configurable
thresholds
Yes
Overvoltage category
III
Input
Recommended
Maximum DC power
3
(Module STC)
2400
3300
3900
4400
5500
6600
6600
W
Transformer-less,
ungrounded
Yes
Maximum input voltage
500
Vdc
1
For model SE5000, it is set to 4985W in Australia, and 4600W in Germany and Czech Republic.
2
16A when the country is set to Denmark, Portugal, UK, or Poland. For other countries, contact SolarEdge.
3
For detailed information regarding allowed oversizing, refer to
http://www.solaredge.com/files/pdfs/inverter_dc_oversizing_guide.pdf