3.2 Basic Features
3.2.1 Features
The T-BAT SYS-HV is one of the advanced energy storage systems on the market
today, incorporating state-of-the-art technology, high reliability, and convenient
control features shown as below:
3.2.2 Certications
3. Product Introduction
3. Product Introduction
10
11
T-BAT system safety
Battery cell safety
UN number
Hazardous materials classication
UN transportation testing requirements
International protection marking
CE, FCC, RCM, TUV (IEC 62619)
UL 1642
UN 3480
Class 9
UN 38.3
IP 55
3.3 Specications
3.3.1 T-BAT SYS-HV Conguration List
3.3.2 Performance
Model Battery Pack Energy(kWh) Voltage (V)No.
1
2
3
4
T-BAT H 5.8
T-BAT H 11.5
T-BAT H 17.3
T-BAT H 23.0
T-BAT H 5.8*1
T-BAT H 5.8*1+HV11550*1
T-BAT H 5.8*1+HV11550*2
T-BAT H 5.8*1+HV11550*3
5.8
11.5
17.3
23.0
100-131
200-262
300-393
400-524
T-BAT H 5.8 HV11550
Dimension(mm)
Weight(kg)
Nominal Voltage(Vdc)
Operating Voltage(Vdc):
Nominal Capacity(Ah):
Max. charge/discharge Current(A) :
Recommend Charge/Discharge Current (A):
Standard Power(kW)
Maximum Power(kW)
474* 193*708
72.2
115.2
100-131
50
35
25
2.5
3.5
474*193*647
68.5
115.2
100-131
50
35
25
2.5
3.5
Altitude(m)
Faradic Charge Eciency( )25°C/77°F
Battery Roundtrip Eciency( /3, )C 25°C/77°F
Expected Lifetime( )25°C/77°F
Cycle life(90% DOD, )25°C/77°F
Available Operating Temperature
Optimal Operating Temperature
Storage Temperature
Ingress Protection
2000
99%
95%
5 years
6000 cycles
0-55°C
15-35°C
-20-5 (3 months)5°C
0- 0 (1 year)4 °C
IP55
Ÿ 90% DOD
Ÿ 99% faradic charge eciency
Ÿ 95% battery roundtrip eciency
Ÿ Cycle life > 6000 times
Ÿ Secondary protection by hardware
Ÿ IP55 protection level
Ÿ Safety & reliability
Ÿ Small footprint
Ÿ Floor or wall mounting