Introduction
12
Diagram B: Neutral line and PE line are combined together, and the emergency
load is connected to the EPS port
.
(For Australia)
BAT
Inverter
Battery
PV Module
Normal Loads
EPS Loads
Diesel Generator
DC Breaker
AC Breaker
AC Breaker AC Breaker
PV1
PV2
GEN
BMS
CT
Grid
GRID
L
N
E-BAR
L N
L N PE L
N
PE
EPS
CT
RCD RCD
N-BAR
Notice!
When power cuts suddenly, the inverter connects the N line of
EPS load with the ground through relay, providing a xed zero
potential for EPS load and ensuring the safety of electricity use
by users.
Ensure that the EPS load rated power is within the EPS rated
output power range, otherwise, the inverter will report an over-
load warning.
Please conrm with the grid operator whether there are special
regulations for grid connection.