109
Operation on LCD
======Pgrid Bias======
Pgrid Bias
> Grid <
b. BIasPower: Default: 40 W, settable range: 1 ~ 300 W (1 ~ 2%*Pn.max)
When you select Grid or INV, the inverter still discharges or charges much power
to or from the grid. Please set Bias Power to limit the charging and discharging
power.
======Pgrid Bias======
Bias Power
> 40 W <
Setting PV connection
This setting depends on the actual connection ways of PV panels.
====PV Connecrion====
PV Mode
> MULTI <
Advanced Password
You can reset the advanced password here.
Shut Down
Shut Down is a function that allows remote control of the inverter to turn on or off with
the local grid instructions, in order to restrict the amount of electricity fed to the grid. This
instruction is implemented by disconnecting or connecting the external switch that is
linked to the inverter.
Function Control: Use COM and Use OFF are available for you to choose.
»
Use COM: Switch on and off the inverter by means of an external switch
connected to the COM communication terminal of the inverter.
»
Use OFF: Switch on and off the inverter by means of an external switch
connected to the OFF communication terminal of the inverter.
======Shut Down======
Function Control
> Use COM <
WaitChargeMode: When Use OFF is selected, the WaitChargeMode interface will
be displayed. This function enables the battery to be charged with photovoltaic
power even when the inverter is in Wait mode.
======Shut Down======
WaitChargeMode
> Enable <