114
Troubleshooting and Maintenance
Error Code Fault Diagnosis and Solutions
IE 04 Grid Freq Fault Grid overfrequency
Wait a moment, if the utility returns to normal, the
system reconnects.
Contact SolaX for help.
IE 05 PV Volt Fault PV overvoltage
Check the output voltage of the PV panel.
Contact SolaX for help.
IE 06 Bus Volt Fault Press the ESC key to restart the inverter.
Check if the PV input open circuit voltage is in the
normal range.
Contact SolaX for help.
IE 07 Bat Volt Fault Battery voltage fault
Check if the battery input voltage is within normal
range.
Contact SolaX for help.
IE 08 AC10mins Volt Grid voltage out of range in the last 10 minutes
The system will return to normal if the grid returns
to normal.
Contact SolaX for help.
IE 09 DCI OCP Fault DCI overcurrent protection fault
Wait for a while to check if it's back to normal.
Contact SolaX for help.
IE 10 DCV OVP Fault DCV EPS (Off-grid) overvoltage protection fault
Wait for a while to check if it's back to normal.
Contact SolaX for help.
IE 11 SW OCP Fault Software detection of overcurrent fault
Wait for a while to check if it's back to normal.
Shut down photovoltaic, battery and grid
connections.
Contact SolaX for help.
IE 12 RC OCP Fault Overcurrent protection fault
Check the impedance of DC input and AC output.
Wait for a while to check if it's back to normal.
Contact SolaX for help.
IE 13 Isolation Fault Insulation fault
Please check the wire insulation for damage.
Wait for a while to check if it's back to normal.
Contact SolaX for help.