161
Appendix
Figure 15-28 Stripping communication cable for meter
c. Connect the conductors to terminal 24 and 25 of the meter.
EP S
Meter Inverter
24 485A Pin 4 485A
25 485B Pin 5 485B
Waterproof distribution box
Figure 15-29 Connecting to meter
Setting Procedure
After connecting meter to the inverter, set parameters on the inverter.
a. Select Menu>Setting>Advance Setting>Meter/CT Setting and enter the Meter/
CT Setting interface according to the setting path.
b. Enable the meter 1 selection and set the meter address and direction. You can
check the connection status in Meter/CT Check.
====Meter/CTSetting====
>Select
Meter
====Meter/CTSetting====
>Select
Enable
====Meter/CTSetting====
>Meter 1 Addr
1
====Meter/CTSetting====
>Meter 1 Direction
Positive