Operation on LCD
heat pump works for them. (see Step C)heat pump works for them. (see Step
C)
c. Set the parameters for mode SmartSave. In this mode, you can set Thresholds
on Feedin power, Thresholds off Consumption, Thresholds off Battery SOC,
Mnimum duration per on-signal, Minimum duration per day and Schedule in
accordance with your actual needs.
===Load Management===
>Mode Select
SmartSave
===Load Management===
>Theresholds on
Feedin power
3000W
===Load Management===
>Minimum duration
per on-signal
5M
===Load Management===
>Theresholds off
Consumption
3000W
===Load Management===
>Minimum duration
per day
900M
===Load Management===
>Theresholds off
Battery SoC
40%
===Load Management===
>Schedule
Enable
• Setting thresholds on/off
»
Thresholds on Feedin power: Once the feed-in power is greater than or
equal to the set value, the Adapter Box will turn on and the heat pump will
heat the water up to a higher temperature.
»
Thresholds off Consumption: Once the power consumption (from the grid)
is greater than or equal to the set value, the Adapter Box will be turned off,
SolaX system stops providing electricity to heat pump.
»
Thresholds off Battery SOC: Once the battery SOC drops to the set value,
the Adapter Box will turn off, SolaX system stops providing electricity to heat
pump.
• Setting minimum / maximum duration
»
Minimum duration per on-signal: Minimum working hours, heat pump will
work at least the time set here every time been activated. High priority than
other power threshold settings.
»
Maximum duration per day: Maximum working hour limitation per day. High
priority than other power threshold settings.
• Setting schedule
»
Schedule: Set the heat pump working periods flexibly (heat pump on and off
periods). High priority than other power threshold settings. Two work periods
can be set.