74
Electrical Connection
7.7.3 Ripple Control Communication Connection
Ripple Control is a common form of grid management. Its communication is based on
superimposing a very high frequency signal onto the 50/60Hz mains power. The inverter
supports to connect a digital signal source (e.g. ripple control receiver) to the digital input.
Requirments for Ripple control
The signal source must be technically suitable for connection to the digital inputs.
(see technial data)
The connected digital signal source has a safe separation to the grid potential.
Connection diagram for ripple control
K1
K2
K3
K4
Ripple control receiver Ripple control terminal
8
7
6
5
4
3
2
1
Figure 7-56 Connection diagram for ripple control
Ripple control wiring procedure
Step 1: Loosen the screws on the COM 2 terminal. Pinch the tabs on the sides of the
COM 2 connector enclosure and pull it at the same time to remove it.
Step 2: Loosen the swivel nut and pull out the sealing plugs. Keep them still in the cable
support sleeve if you choose not to connect the cable.
Remove
1
2
3
Figure 7-57 Disassembling the connector