Faults
Diagnosis and solution
SW_OVP_Boost
SW_OVP_ACR
SW_OVP_BUS
Iso l Fault
SW_OCP_DCI
Boost over voltage detected by software.
Check the PV input,make sure the Max.DC voltage is 950V.
Or seek help from us.
SW_OVP_Boost I
SW_OVP_Boost II
SW_OVP_ACS
SW_OVP_ACT
SW_UVP_ACR
SW_UVP_ACS
SW_UVP_ACT
SW_OFP_AC
SW_UFP_AC
SW_UFP_ACR
SW_UFP_ACS
SW_UFP_ACT
SW_OFP_ACR
SW_OFP_ACS
SW_OFP_ACT
Iso Il Fault
RelayShortFault
RelayOpenFault
Over current/voltage of each phase in AC side detected
If one of the fault happens frequently,please contact with the
dealer to check the nearest transformer.
by software.
Or seek help from us.
Bus over voltage detected by software.
Check the PV input,make sure the Max.DC voltage is 950V.
Or seek help from us.
If this happens frequently,please contact with the grid Corp.,
get the password to set the value.(VDE4105)
Or seek help from us.
The grid frequency is out of limit.
Isolation fault in boost circuit.
Please check the PV input wire.
Or seek help from us,
The relay in the inverter is fault.
Please contact with us.
DCI current over limit.
Please contact with us.
Faults
Diagnosis and solution
SW_OCP_RCD_Jump II
SW_OVP_ACRMS
SW_OverTemp
Residual current detector device fault or residual current
Check the impedance of DC input and AC output.
Or seek help from us.
SW_OCP_RCD
SW_OCP_RCD_Jump I
SW_IACRMS_Unblance
SW_FAN I fault
The RMS value of AC current is over limit.
If this happens frequently,please contact with us.
Temperature is over limit.
Or seek help from us.
The RMS value of AC current not balance.
SW_OCP_RCD_Jump III
SW_OCP_RCD_300mA
over limit,
Check if fan is running normally.
Check if the environment temperature is over limit.
Fan fault.
Or seek help from us.
Check if fan is running normally.
Check if anything block the fan.
SW_FAN II fault
SW_FAN III fault
UnRecover_LN_Fault
The L and N line is not correctly connected.
Or seek help from us.
Check the connection of L and N.
Auto_Test_Fault
Auto test failed.(For Italy)
SW_BUS_Unblance
Bus not balance.
Contact with us if this happens frequently.
PhaseDelta Fault
Phase fault.
Contact with us if this happens frequently.
Control Loop ERR
Controller fault.
Contact with us if this happens frequently.
43
42
7 Troubleshooting 7 Troubleshooting