EasyManuals Logo

Square D I-Line User Manual

Default Icon
188 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
© 2013–2017 Schneider Electric Reservados todos los derechos
Tableros de distribución combinados I-Line™ 80043-808-02 Rev. 02
Anexo 1: Especificaciones—Corriente nominal de cortocircuito adicional 03/2017
46
ESPAÑOL
240 3P/3W or
240 1P/2W
(two pole only)
25,000 LD
QO (B) VH 15–150 A
QO (B) EPD 15–30 A
QO (B) EPE 15–30 A
42,000
LA, MA QDL 70–225 A 70–225 A
LC 400 A QO (B) VH 15–100 A
LC 600 A QO (B) VH 15–100 A
MG QO (B) VH 150 A
65,000
LC 400 A QO (B) VH 15–100 A
LC 600 A QO (B) VH 15–30 A
DJ 400 A
QO (B) VH 15–150 A
QO (B) H 15–100 A
DJ, DG, DL
150–600 A
QO (B) EPD 15–30 A
QO (B) EPE 15–30 A
EG, FG, KG
QO (B) 15–100 A
QO (B) GFI 15–50 A
QG
QO (B) 15–30 A
QO (B) VH 35–150 A
QO (B) H 15–100 A
QG, HG, JG QO (B) PL 15–30 A
HG, JG
QO (B) 15–100 A
QO (B) VH 35–150 A
QO (B) H 15–100 A
FC_ or
KC_22___
QO (B) 15–100 A
FC_ or
KC_34___
QO (B) AS 15–30 A 15–30 A
LG
QO (B) VH 15–150 A
QO (B) H 15–100 A
QO (B) EPD 15–30 A
QO (B) EPE 15–30 A
LJ
QO (B) EPD 15–30 A
QO (B) EPE 15–30 A
LL
QO (B) EPD 15–30 A
QO (B) EPE 15–30 A
Table 8: Series Connected Breaker Ratings (RMS Symmetrical) (continuación)
Max.
System
Voltage
AC
1, 2
Max.
Short
Circuit
Current
Rating
Square D Brand
Integral or Remote
Main Circuit Breakers
and Remote
Main Fuses
Square D Brand Branch Circuit Breaker
Catalog Designation and Allowable
Ampere Ranges
3, 4, 5, 6
Type 1 Pole 2 Pole 3 Pole
80043-808-01.book Page 46 Wednesday, March 22, 2017 12:31 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Square D I-Line and is the answer not in the manual?

Square D I-Line Specifications

General IconGeneral
Bus MaterialAluminum or Copper
Voltage Rating600V AC
Current RatingUp to 1200A
EnclosureNEMA 1
Poles2, 3
Interrupting Rating200 kA (depending on the specific model and installed breakers)