© 2013–2017 Schneider Electric All Rights Reserved
80043-808-02 Rev. 02 I-Line™ Combo Switchboards
03/2017 Specifications—Lighting Section Ratings
45
ENGLISH
240/120
3P/4W
125,000 HL, JL
QO (B) 15–70 A 15–125 A 15–100 A
QO (B) H — 15–100 A —
QO (B) VH — — 35–150 A
QO (B) PL 15–30 A 15–60 A 15–30 A
QO (B) GFI 15–30 A 15–60 A 15–50 A
QO (B) EPD 15–30 A 15–60 A 15–50 A
QO (B) AFI 15–20 A — —
QO (B) CAFI 15–20 A — —
QO (B) DF 15–20 A — —
200,000 FI, KI, HR, JR
QO (B) 15–70 A 15–125 A 15–100 A
QO (B) GFI 15–30 A 15–60 A —
QO (B) EPD 15–30 A 15–60 A —
QO (B) AFI 15–20 A — —
QO (B) CAFI 15–20 A — —
QO (B) DF 15–20 A — —
240 3P/3W or
240 1P/2W
(two pole only)
22,000
QO (B) VH
QO (B) — — 15–100 A
QO (B) GFI — — 15–50 A
QO (B) PL — 15–30 A —
Q2-H QO (B) — — 15–30 A
25,000
QD
QO (B) — — 15–30 A
QO (B) VH — — 35–150 A
QO (B) H — 15–100 A —
QO (B) PL — 15–60 A 15–30 A
QO (B) EPD — — 15–50 A
QO (B) EPE — — 15–50 A
QO (B) GFI — — 15–50 A
ED, FD
QO (B) — — 15–100 A
QO (B) GFI — — 15–50 A
KD QO (B) — — 15–100 A
HD, JD
QO (B) — — 15–100 A
QO (B) VH — — 35–150 A
QO (B) H — 15–100 A —
QO (B) GFI — — 15–50 A
Continued on next page
Table 8: Series Connected Breaker Ratings (RMS Symmetrical) (continued)
Max.
System
Voltage
AC
1, 2
Max.
Short
Circuit
Current
Rating
Square D Brand
Integral or Remote
Main Circuit Breakers
and Remote
Main Fuses
Square D Brand Branch Circuit Breaker
Catalog Designation and Allowable
Ampere Ranges
3, 4, 5, 6
Type 1 Pole 2 Pole 3 Pole
80043-808-01.book Page 45 Wednesday, March 22, 2017 12:31 PM