SL800, 800 A
S33931, 1200 A
1
LC/LX 2, 3 600
100 240
65 480
35 600
LI/LXI 2, 3 600
200 240
200 480
100 600
MA 2, 3 800
42 240
30 480
22 600
MH/MX 2, 3 800
65 240
65 480
25 600
SL800M5, 800 A
SL1200P5, 1200 A
SL1200P6, 1200 A
SL1200P7, 1200 A
MG, PG 2, 3 800
65 240
35 480
18 600
MJ, PJ 2, 3 800
100 240
65 480
25 600
PK 2, 3 800
65 240
50 480
50 600
PL 2, 3 800
125 240
100 480
25 600
MA/MH/MX 2, 3 800
65 240
65 480
25 600
SL1200P5, 1200 A
1
SL1200P6, 1200 A
1
SL1200P7, 1200 A
1
PG 2, 3 1200
65 240
35 480
18 600
PJ 2, 3 1200
100 240
65 480
25 600
PK 2, 3 1200
65 240
50 480
50 600
PL 2, 3 1200
125 240
100 480
25 600
Table 9: Short Circuit Current Ratings for Plug-On Lugs with
Protective Circuit Breakers (continued)
Catalog Number
and Ampere
Rating
Protecting Circuit Breakers
Maximum Available
Short Circuit Current
Catalog
Prefix
Number
of Poles
Maximum
Amperes
RMS Sym.
kA
Volts AC
80043-808-01.book Page 54 Wednesday, March 22, 2017 12:31 PM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Square D I-Line and is the answer not in the manual?

Square D I-Line Specifications

General IconGeneral
Bus MaterialAluminum or Copper
Voltage Rating600V AC
Current RatingUp to 1200A
EnclosureNEMA 1
Poles2, 3
Interrupting Rating200 kA (depending on the specific model and installed breakers)