Tableros de distribución combinados I-Line™ 80043-808-02 Rev. 02
Anexo 1: Especificaciones—Valores nominales de la sección I-Line 03/2017
28
ESPAÑOL
600
18,000
HG, JG FA, HD
2, 3
JG JD
MG, PG, RG HD, JD
MG FA
LG LD 3
LG HD, JD
2, 3
25,000
HJ, JJ FA, HD, HG
JJ JD
PJ, RJ MG
LJ LD, LG 3
LJ JD, JG, HD, HG, MA
2, 3
35,000 LC
FH, HD, HG, HJ, JD, JG, JJ,
LA
50,000
HL, JL FA, HD, HG, HJ
JL JD, JG, JJ
PK HJ, JJ, MJ
LL LD, LG, LJ 3
LL HD, HG, HJ, JD, JG, JJ, MA
2, 3
100,000
FI, KI HD, HG, HJ
KI JD, JG, JJ
HR FA, HD, HG, HJ, HL
JR
FA, HD, HG, HJ, HL,
JD, JG, JJ, JL
KI, LI FH
LI LA
347
18,000
BG6, HG, JG, LG, MG,
PG
BD6 (60 A Max.)
1
25,000
BJ, HJ, JJ, LJ, MJ, PJ BD6, BG6 (60 A Max.)
100,000 HR, JR BD6, BG6, BJ (60 A Max.)
Tabla 3: Valores nominales de los interruptores automáticos conectados en
serie (rcm simétricos) (continuación)
Tensión máxima
del sistema
de ~
2
Corriente
nominal máxima
de cortocircuito
Interruptor
automático principal
integral o remoto
marca Square D, de
2 ó 3 polos
1
Interruptor automático derivado
marca Square D
Designación de no. de
catálogo
Polos
80043-808-01.book Page 28 Wednesday, March 22, 2017 12:31 PM