Repair instructions
HPG-I 04-06-08-12-15 S-CS-DS-DCS
Premium
Condenser outlet sensor value is outside
the permissible value range.
Check the sensor, its wiring and the
associated connectors, replace if defective.
Sensor value of oil sump temperature
sensor is out of range
of the permissible range of values.
Check the sensor, its wiring and the
associated connectors,
Replace if defective.
The communication with the FES does not
work correctly.
Check the terminal point of the
communication cable or change the
communication cable.
Superheating of the refrigerant at the
evaporator outlet or at the
Compressor inlet too long below the
permitted limit value.
Expansion valve is not working properly.
Unexpectedly high deviation of the
expansion valve opening degree from
the pilot curve.
Refrigerant leakage. Expansion valve is not
working properly.
Volume flow monitoring from heating
output, flow temperature and return
temperature.
Compressor speed deviation between
setpoint and actual value.
Frequency converter or compressor not
working correctly
Inverter main fault: Inverter IGBT
overcurrent.
Inverter main fault: PFC IGBT
overcurrent.
Inverter main fault: DC link overvoltage.
Inverter main fault:
DC link undervoltage.
Inverter main fault: AC voltage input
Undervoltage.
Inverter main fault: AC voltage input
overvoltage.
Inverter main fault: Voltage differences
between the
three input phases.
Inverter main fault: Desaturation
Inverter main fault: Inverter IGBT
overtemperature.
Inverter main fault: Inverter PFC IGBT
overtemperature.
Inverter main error: Rotor does not
rotate as expected.
Inverter main error: Arithmetic error in
the measurement and analysis process.
Inverter main fault: Input relay open.
Inverter main fault: Current differences
between the three inverter IGBTs.
Inverter main fault: Current differences
between the three inverter PFC IGBTs.
Inverter main error: Low voltage range
exceeded.