4
2 Specification
2.1 Data table
The output details refer to new appliances with clean heat exchangers.
The power consumption of the integral auxiliary drives represents the maximum value and may vary subject to operating point.
The power consumption of the integral auxiliary drives is included in the output details of the appliance (to EN 14511).
WPL 33
Bestellnummer 185348
Outputs to EN 14511
Output at A10/W35 (EN 14511) kW 15,10
Heating output at A10/W35 twin compressor operation (EN 14511) kW 20,70
Output at A7/W35 (EN 14511) kW 12,61
Output at A2/W35 (EN 14511) kW 10,78
Heating output at A2/W35 twin compressor operation (EN 14511) kW 17,70
Output at A-7/W35 (EN 14511) kW 8,90
Heating output at A-7/W35 twin compressor operation (EN 14511) kW 14,90
Power consumption
Power consumption, emergency/booster heater kW 8,8
Power consumption, fan heating max. kW 0,27
Power consumptions to EN 14511
Power consumption at A10/W35 (EN 14511) kW 3,70
Power consumption at A7/W35 (EN 14511) kW 3,50
Power consumption at A10/W35 twin compressor operation (EN 14511) kW 6,30
Power consumption at A2/W35 (EN 14511) kW 3,31
Power consumption at A-7/W35 (EN 14511) kW 3,20
Power consumption at A-7/W35 twin compressor operation (EN 14511) kW 5,80
Power consumption at A2/W35 twin compressor operation (EN 14511) kW 6,10
Coefficients of performance to EN 14511
Coefficient of performance at A10/W35 (EN 14511) 4,10
Coefficient of performance at A10/W35 twin compressor operation (EN 14511) 3,30
Coefficient of performance at A7/W35 (EN 14511) 3,60
Coefficient of performance at A2/W35 (EN 14511) 3,26
Coefficient of performance at A2/W35 twin compressor operation (EN 14511) 2,90
Coefficient of performance at A-7/W35 twin compressor operation (EN 14511) 2,60
Sound data
Sound power level (EN 12102) dB(A) 65
Sound power level - external installation with silencer accessories dB(A) 63
Sound power level, internal installation (EN 12102) dB(A) 58
External sound power level, external installation (EN 12102) dB(A) 65
Sound power level - external installation without silencer accessories (EN 12102) dB(A) 65
Sound pressure level at 1 m distance in a free field dB(A) 57
Sound pressure level at 5 m distance in a free field dB(A) 43
Sound pressure level at 10 m distance in a free field dB(A) 37
Application limits
Min. application limit on the heating side °C 15
Max. application limit on the heating side °C 60
Heat source application limit (min.) °C -20
Heat source application limit (max.) °C 30
Electrical details
Frequency Hz 50
Emergency/booster heater fuse A 3 x B 16
Control circuit fuse A 1 x B 16
Fuse - compressor A 3 x C 25
Rated voltage, emergency/booster heater V 400
Rated control voltage V 230
Rated compressor voltage V 400
Phases, emergency/booster heater 3/N/PE
Control phases 1/N/PE
Compressor phases 3/PE
Current (with/without softstarter) A <30/-
Versions
Condenser material 1.4401/Cu
Refrigerant R407 C
Refrigerant capacity kg 4,4
Compressor oil Emkarate RL 32 3MAF / MOBIL EAL Arctic 22 CC
Defrost method Circuit reversal
IP-Rating IP14B
Dimensions
Height mm 1116
Width mm 784
Depth mm 1332