4.9 Connection array WPMS II
Make the WPMS II connections in accordance with the connection array shown. For this, insert the plugs supplied as follows onto the WPMS II to
provide a complete complement:
LV area
X10
1 Heat meter pulse input
2 Earth
X11
1 HP flow sensor
2 Earth
3 HP return sensor
4 Earth
5 Analog output 0 -10 V
6 DHW cylinder sensor
7 Rotary selector for heat metering
DHW cylinder bottom for solar heating connection
8 Sensor second heat source
9 Flow sensor for heat metering
Collector sensor for solar heating connection
10 Outside temperature sensor
X12
1 Earth
2 Source sensor
X13
1 Earth
2 Mixer flow sensor
X14
1 Remote control
2 Earth
3 Remote control
X15
1 BUS high
2 BUS low
3 Ground „–“
4 „+“ (only connected in accordance with the “DCOactiv” controller )
Mains voltage area
X20
1 Mixer circuit pump
2 Source pump
3 ESC enable signal (must be connected)
4 Solar heating pump
5 N
X21
1 Mixer OPEN
2 Mixer CLOSE
X22
1 N
2 L
3 L* (voltage input for relay outputs)
4 DHW circulation pump
5 Buffer loading pump 1
6 Buffer loading pump 2
7 DHW loading pump
8 Heating circuit pump 1
9 Second Heat source zero-volt
10 Second Heat source contact
26_03_01_0246
Internal
wiring