Second control level (P parameters):
Setting of control parameters
Simultaneously pressing the UP and DOWN key for at least 4 seconds opens a parameter list
containing control parameters.
With the UP and DOWN keys the list can be scrolled in both directions.
Pressing the SET key will give you the value of the respective parameter. Pressing also the UP or
DOWN key at the same time the value can be adjusted.
Return to the initial position takes place automatically, if no key is pressed for 60 seconds.
Para-
meter
Function description
Adjustment range
Standard
setting
Custom
setting
P0
Actual measuring value
-
-
P2
Hysteresis contact K1
0.1... 99.9 K
1.0 K
P4
Control range limitation
minimum setpoint
-99°C...P5
-99°C
P5
Control range limitation
maximum setpoint
P4...999°C
999°C
P6
Actual value correction
-20.0...+20.0 K
0.0 K
P19
Key-lock
0: no key-lock
1: key-lock
0
P30
Lower alarm value
-99 ... 999°C/K
-99°C
P31
Upper alarm value
-99 ... 999°C/K
100°C
P32
Hysteresis alarm circuit
0.1... 99.9 K
1.0 K
d0
Defrosting interval
1...99 hours
0: no defrosting
8 h
d2
Defrosting temperature
-99 …999 °C
10.0 °C
d3
Defrosting time limit
1…99 min
0: without time limit
30 min

Questions and Answers: