(213): Battery current limitation by the
BSP stopped
Message sent by master 2 seconds after stopping to
receive a signal for limiting the current from the BSP.
Warning (214): Half period RMS
voltage limit exceeded, transfer
opened
An AC voltage lower than the minimum limit
{1200} was detected (during half a sine wave)
and the transfer relay opened.
Warning (215): UPS limit reached,
transfer opened
The UPS part detected a loss of AC-In (mode
{1552} and sensibility function {1510}), therefore
the transfer relay opened.
Warning (216): Scom watchdog
caused the reset of Xcom-232i
Problem with SCOM protocol. See the technical
description of the SCOM protocol, available on
Studer website, for more information.
Warning (217): CAN problem at
Xtender declaration
Problem with the Xtender announcing itself (old
version of communication bus CAN1).
Warning (218): CAN problem while
writing parameters
The system tried to write a parameter 3 times
without any success. Check the CAN bus wiring
and the CAN bus terminations.
(222): Front ON/OFF button pressed
The front on/off button was pressed.
The main off was performed.
(224): Delay before closing transfer
relay in progress {1580}
Generator preheating has started.
Halted (255): Incompatible devices,
update mandatory