STULZ Ultra-Series Humidifier Controller
26
(Augu
st,
201
3)
Alarm
CONTROL
Service
Version
SET
Alarm Set
Cntrl Set Point: 45.0%
STATUS--------------------
Temp: 67.8°F
Hum: 38.9%
Dew: 41.7°F
Cntrl Set Point: 45.0°F
STATUS--------------------
Temp: 67.8°F
Hum: 38.9%
Dew: 41.7°F
5.4 Control Menu
From the Control Menu 4 menus may be selected: Set
points, Alarm Set points, Clock and Version. The controller
may be programmed by the user to require level 1
password authorization to enter this menu (see Section
4.3). Once password access is granted, selecting and
adjusting basic settings controlling the performance of the
system, enabling alarms and determining their set points
and setting the clock is allowed. Some fields in the Control
Menu screens are read only.
Set Point Screens
5.4.1
Press Enter
() at this screen to enter into the Set Point
screens.
5.4.1.1 Humidity Control Set Point
If humidity control is selected, the Humidity Control screen
shows the current set point and the conditions related to
control. If the control temperature sensor is enabled, the
“Temp” and “Dew” will be visible. If the control temperature
sensor is not enabled, they will not appear. Press the
Enter () at this screen to enter move to the set point
value. Use the Up () and Down () keys to change the
value. When the desired value is displayed, press the
Enter () key. The cursor will return to the upper left hand
corner, allowing the use of the Up () and Down () keys to
move to the next set point.
5.4.1.1 Dew Point Control Set Point
If dew point control is
selected, the Humidity Control
screen shows the current set point and the conditions
related to control. Press the Enter () at this screen to
enter move to the set point value. Use the Up () and
Down () keys to change the value. When the desired
value is displayed, press the Enter () key. The cursor will
return to the upper left hand corner, allowing the use of the
Up () and Down () keys to move to the next set point.
5.4.1.1 Humidity Limit Set Point
The Limit Set Point field appears if the E-Ultra controller is
configured with an optional remote humidity sensor. The
sensor may be located in the duct downstream of the
Humidifier where condensation could form. A value is
entered in the Limit Set Point field to limit humidity
production based on a remote humidity or dew point
sensor input to prevent condensation from forming in the
duct. If the limit temperature sensor is enabled, the “Temp”
and “Dew” will be visible. If the limit temperature sensor is
not enabled, they will not appear. Press the Enter () at
this screen to enter move to the set point value. Use the
Up () and Down () keys to change the value. When the
desired value is displayed, press the Enter () key. The
cursor will return to the upper left hand corner, allowing the
use of the Up () and Down () keys to move to the next
set point.
Main Menu
Control
Humidity Control
dew point Control

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Stulz Ultra Series and is the answer not in the manual?

Stulz Ultra Series Specifications

General IconGeneral
BrandStulz
ModelUltra Series
CategoryController
LanguageEnglish

Related product manuals