Backwash-Valve setup (Besgo or Pneumatic)
Be sure that the equipment has this feature enabled. Go to the menu item Extra Settings and
check if the option Backwash appears listed.
Main Menu -> Settings -> Service menu -> Installer -> Extra settings -> Backwash
If it is not listed, you must send the equipment to Sugar Valley to activate that function.
If the option appears, select the desired valve type.
Main Menu -> Settings -> Service menu -> Installer -> Extra settings -> Backwash
None/Besgo/Pneumatic
We have to choose between Besgo or pneumatic.
To set up a Backwash valve, we have to assign a free power relays, AUX2 for instance.
Main Menu -> Settings -> Service menu -> Installer -> Relay config. -> Backwash
AUX2